APPLICATION
Servers, Data-centers, Critical network devices, Sensitive electronic equipment, Telecom...
KEY FEATURES
l DSP Control l Fully digital control technology provides a highly accurate,drift-proof control compared to traditional analog electronics l Optional language by LCD dispaly(English,russian,German,French,Spanish) l Input power factor is more than 0.98,Output power factor is 0.9 l Optional output frequency,50 or 60HZ automatic or configurable as a frequency converter l Batttery intelligent management l Smart RS-232,intelligent slot,USB and EPO communication port
TECHNICAL SPECIFICATIONS
MODEL |
|
H1K |
H1KS |
H2K |
H2KS |
H3K |
H3KS |
CAPACITY |
VA/W |
1000VA/900W |
2000VA/1800W |
3000VA/2700W |
INPUT |
Nominal Voltage |
100/110/120/127 VAC or 200/208/220/230/240 VAC |
Operating Voltage Range |
60-138VAC or 120-276VAC |
Frequency Range |
40 to 70 Hz before transfer to battery , automatic selection of nominal frequency 50/60Hz for Inverter to match Input (Auto Sync.) |
Phase |
Single Phase |
Power Factor |
> 0.98 |
Cold Start(0 to 100% load) |
Yes |
OUTPUT |
Voltage |
100, 110, 120, 127 VAC(±2%) or 200, 208, 220, 230, 240 VA(±2%) |
Frequency |
50 or 60 Hz Automatic or configurable as a frequency converter |
Wave form |
Sine Wave |
Power Factor |
0.9 |
Voltage Distortion |
R Load: < 3 % THD;RCD Load: < 5 % THD |
Overload Capacity |
Transfer to bypass if available or else shut down after the following:100% < load < 102%,overload warning;102% < load < 130%, 12s;130% < load < 150%, 2s |
Current Crest Ratio |
3:1 |
Connection |
Hardwired |
EFFICIENCY |
|
>82% (1 kVA) >84% (2-3kVA) |
BATTERY |
Type |
Valve Regulated Lead Acid (VRLA), minimum 3 years float service life at 25℃ |
Nominal DC Voltage |
36VDC |
36VDC |
96VDC |
96VDC |
96VDC |
96VDC |
Quantity |
3x12V/7Ah |
|
3x12V/7Ah |
|
8x12V/7Ah |
|
TRANSFER TIME |
0ms(no break) in Online mode, 5 ms max in High Efficiency mode due to loss of utility |
Bypass |
|
Automatic bypass to provide an alternate path to utility power in the case of overload, or internal failure |
|
Bypass is permitted only when Frequency is within ±5 HZ of nominal and Voltage is within +10 / -15 V (CS) of nominal outside this range bypass is NOT AVAVAILABLE and WILL NOT occur (CS) |
User interface |
LCD display |
UPS status, I/P& O/P voltage & frequency,Battery voltage,Battery capacity,Loading, Temprature, History record |
Language |
English, German, French, Spanish, Russian (other language packs can be loaded) |
Communications |
DB-9 port |
RS-232, XCP, Relay mode |
Intelligent Slot |
Options: SMNP Card, AS400 Card or Winpower CMC / USB Por |
Enviromental |
Operating temperature |
(at sea level) 0-40℃ Online Mode. The unit will be derated linearly for altitude, Max altitude refer to 10.5. |
NOTE: Thermal protection in case of overheating switches Load to Bypass. |
Operating humidity |
5 - 90% Non-condensing |
Acoustic Noise |
<45dB <45dB <50dB (2000~3000VA) |
Physical Fea |
Weight |
15 7.5 33.5 14 34 14.5 |
Dimensions(H x W x D)mm |
230.6x160x350 230.6x160x350 325x214x380 325x214x380 325x214x380 325x214x380 |
Specifications are subject to change without notice
|