Uses:
Just the way the fire is only the power facility or a load in the motor to provide a variable-frequency three-phase emergency power system to address the emergency power supply and the motor to start the process of the impact of power supply equipment. Such as: fan motor electric motor or other equipment.
Scope of application:
High-rise building elevators, central air-conditioning, fire pumps, exhaust fans, fire and industrial sector, power use.
3 INPUT AND 3 OUTPUT SERIES: EPS TECHOLOGY PAREMETER SHEET | |
EPS-15KW |
EPS-15KW |
EPS-18.5KW |
EPS-22KW |
EPS-30KW |
EPS-37KW |
EPS-45KW |
EPS-55KW |
EPS-75KW |
EPS-93KW |
EPS-110KW |
EPS-132KW |
EPS-160KW |
MOST OUTPUT CURRENT |
28A |
42A |
56A |
85A |
113A |
141A |
169A |
205A |
255A |
304A |
360A |
450A |
WORKING MODE&PRINCIPIUM |
ONLINE POWER SUPPLY STATIC STATE BYPASS SWITH (UNINTERRUTIBLE POWER SWITCH ) TWIN CHANGING TECHNOLOGY COMPLETE INSULATING POWER SUPPLY |
INPUT VOLTAGE |
380VAC±25%(3 INPUT & 3 OUTPUT)+N+G |
FREQUENCY |
50HZ±10%, 60HZ±10% |
OUTPUT VOLTAGE |
380VAC±1% ( load in steady) |
FREQUENCY |
50HZ±0.2%, 60HZ ± 0.2% (SUPPLY POWER FROM BATTERIES) |
WAVE AND SUMMIT RATE |
3:01 |
WAVE DISTORTATION |
LINEARY<3%,NON-LINEARY <5% |
LOADING VOLTAGE CHANGE (FROM 0 TO 100%) |
<±5% |
BATTERIES QUANTITY |
32 CELLS |
33 CELLS |
40 CELLS |
BATTERIES VOLTAGE |
384VDC |
396VDC |
480VDC |
TRANFORMATION TIME |
<100MS |
OVER-LOADED CAPACITY |
125% 10 MIN, 150% 1 MIN |
WORK EFFECIENCY |
93% |
93% |
94% |
94% |
95% |
95% |
95% |
96% |
VOICE DISTANCE 1 METER |
48--60DB |
53--65DB |
COOL WAYS |
COMPULSORY VENTILATION |
|
RELATIVE HUMIDITY(NON-CONDENSE) |
5%--95% |
COMPUTER COMMUNICATION PORT |
RS232 / RS422 |
OUT SIZE (W X H X D mm) |
560 x 1140 x 80 |
560 x 1400 x 800 |
950 x 1800 x 850 |
1200 x 1800 900 |
WEIGHT (kg) |
210 |
258 |
350 |
400 |
480 |
580 |
650 |
900 |
1200 |
1300 |
1350 |
1480 | |